Categories
Article No. 296.045.573
E-Number 808 487 000
Technical specification
SPD type T1 / T2  
Number of poles 3  
max. discharge current (Imax) 50 kA  
Nominal line voltage Un AC 230 V  
Continuous voltage AC max. 280 V  
Nominal frequency [fn] 50 - 60 Hz
Impulse current [Iimp]_(10/350) 12.5 kA  
Discharge current max. (8/20) µs [Imax] 50 kA  
Nominal discharge surge current (8/20) 20 kA  
Voltage protection level [Up] 1.3 kV  
Follow current [IF] 0 kA  
follow current extinguishing capability [Ifi] unendlich kA eff  
Response time [ta] 0 ns  
TOV-voltage L-N [UT] 440 Vac  
Short circuit resistance (Icw) 25 kA  
Fault indication Mechanisch, Rot  
Temperature range -40 - 85 °C
Degree of protection IP 20  
Fuse max. (gG) 160 A  
Mounting on Hutschiene 35 mm  
Signaling on the device Optic  
Signaling contact Yes  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
Energetically coordinated protective effect to the terminal Yes  
Nominal cross section conductor 0 - 42 mm²  
Technische Spezifikation
Material housing Thermoplastik UL-94-V0  
Technical specification
Mounting method DIN rail (top hat rail) 35 mm  
Remote signalling Yes  
Degree of protection (IP) IP20  
Construction size 3 modular spacing  
Voltage protection level L-N [Up] 1.3 kV  
Total discharge current (8/20) (L N-PE) 50 kA  
Standards
Homologation VDE, ÖVE und UL  
Test standards International IEC 61643-11  
Test standards USA UL 1449 ed.3  
Test standards Europe EN 61643-11  
Commercial specification
Customs number 85363000  
country of origin undefined  
Logistic specification
VPE Weight 0.444 kg  
Replacement module

Replacement module 296.045.570

More