Photovoltaics surge protection T1+T2 DS 60 VGPVS
Characteristics
- Surge protector photovoltaic type 1+2
- 10 years warranty
- limp = 12.5kA/pole (10/350µs)
- internal disconnection, status indicator
- follow and operating current: none
- remote signaling
SPD type
T1 / T2
Signaling contact
Yes
Impulse current [Iimp]_(10/350)
12.5 kA
max. discharge current (Imax)
40 kA
Response time [ta]
0 ns
Nominal discharge surge current (8/20)
20 kA
Number of poles
2
Nominal cross section conductor (min/max)
6.0 - 35.0 mm²
Discharge current max. (8/20) µs [Imax]
40 kA
Operating current [Ic]
0 kA
Follow current [IF]
0 kA
follow current extinguishing capability [Ifi]
Unendlich kA eff
Short circuit resistance (Icw)
25 kA
Fault indication
Mechanisch, Rot
Temperature range
-40.0 - 85.0 °C
Degree of protection
IP20
Material housing
Signaling on the device
Optic
Connection cross section solid / stranded max.
1.5 mm²
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)
Energetically coordinated protective effect to the terminal
Yes
System configuration DC
Yes
Construction size
4 modular spacing
20/Pol
Integrated backup fuse
No
Exhausting
No
Number of poles
2
Mounting method
DIN rail (top hat rail) 35 mm
Degree of protection (IP)
IP20
Test standards Germany
Test standards USA
UL 1449 ed.3
Test standards Europe
FprEN 50539-11
Test standards France
UTE C61-740-51
Homologation
VDE, ÖVE und UL