Categories

Photovoltaics surge protection T1+T2 DS 60 VGPVS

Characteristics
- Surge protector photovoltaic type 1+2
- 10 years warranty
- limp = 12.5kA/pole (10/350µs)
- internal disconnection, status indicator
- follow and operating current: none
- remote signaling

SPD type
T1 / T2  
Signaling contact
Yes  
Impulse current [Iimp]_(10/350)
12.5 kA  
max. discharge current (Imax)
40 kA  
Response time [ta]
0 ns  
Nominal discharge surge current (8/20)
20 kA  
Number of poles
2  
Nominal cross section conductor (min/max)
6.0 - 35.0 mm²
Discharge current max. (8/20) µs [Imax]
40 kA  
Operating current [Ic]
0 kA  
Follow current [IF]
0 kA  
follow current extinguishing capability [Ifi]
Unendlich kA eff  
Short circuit resistance (Icw)
25 kA  
Fault indication
Mechanisch, Rot  
Temperature range
-40.0 - 85.0 °C
Degree of protection
IP20  
Material housing
 
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
Energetically coordinated protective effect to the terminal
Yes  
System configuration DC
Yes  
Construction size
4 modular spacing  
20/Pol  
Integrated backup fuse
No  
Exhausting
No  
Number of poles
2  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
Test standards Germany
 
Test standards USA
UL 1449 ed.3  
Test standards Europe
FprEN 50539-11  
Test standards France
UTE C61-740-51  
Homologation
VDE, ÖVE und UL  
   
Article No. E-Number SPD type Signaling contact Impulse current [Iimp]_(10/350) max. discharge current (Imax) Operation voltage max. [Uc] Response time [ta] Voltage protection level [Up] Nominal discharge surge current (8/20) Number of poles Nominal cross section conductor (min/max) VPE Quantity
   
Photovoltaics surge protection 296.045.923 808 486 100 T1 / T2 Yes 12.5 40 ≤500VDC 0 1.7 20 2 6.0 - 35.0 1
Photovoltaics surge protection 296.045.973 808 486 300 T1 / T2 Yes 12.5 40 ≤1200VDC 0 2.8 20 2 6.0 - 35.0 1