Categories

Junction box PV GAK 210-MC4 b

Characteristics
Generator boxes with preassembled surge protection:

Legend
a) type 1+2 GAK + 60 VGPVS-1000-4ST-2MPP
b) type 1+2 GAK + 50 PVS-1000-4ST-2MPP
c) type 1+2 GAK + 50 VGPVS-1000-4ST-2MPP
d) type 2 GAK + 50 PV-1000-4ST-2MPP
e) type 1+2 GAK + 60 VGPVS-1000-3ST-1MPP/1ST-1MPP
f) type 1+2 GAK + 50 PVS-1000-3ST-1MPP/1ST-1MPP
g) type 1+2 GAK + 50 VGPVS-1000-3ST-1MPP/1ST-1MPP
h) type 2 GAK + 50PV-1000-3ST-1MPP/1ST-1MPP

SPD type
T1 / T2  
Operation voltage max. [Uc]
≤1200VDC  
Number of poles
2  
Nominal line voltage Un DC
1000 V  
Protection level max. (at 5kA)
2.1 kV  
Protection level max. (at 12.5kA)
2.3 kV  
Operating current [Ic]
0 kA  
Follow current [IF]
0 kA  
follow current extinguishing capability [Ifi]
Unendlich kA eff  
Fault indication
mechanisch, Rot  
Temperature range
-40.0 - 85.0
Fault indication
Mechanisch, Rot  
Temperature range
-40.0 - 85.0
Material housing
 
Signaling on the device
optisch  
Material housing
 
Degree of protection
IP20  
Signaling on the device
optisch  
Material housing
 
Signaling on the device
optisch  
Energetically coordinated protective effect to the terminal
Yes  
Energetically coordinated protective effect to the terminal
Yes  
System configuration DC
Yes  
Energetically coordinated protective effect to the terminal
Yes  
System configuration DC
Yes  
System configuration DC
Yes  
Integrated backup fuse
No  
Exhausting
No  
Integrated backup fuse
No  
Exhausting
No  
Integrated backup fuse
No  
Mounting method
DIN rail (top hat rail) 35 mm  
Exhausting
No  
Total discharge current (8/20) (L N-PE)
60 kA  
Mounting method
DIN rail (top hat rail) 35 mm  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
Degree of protection (IP)
IP20  
Connection cross section solid / stranded max.
1.5 mm²  
degree of protection
IP65  
number of modules
20  
contract rail
DIN-Schiene  
String / MPP
4ST-2MPP  
inputs PG / MC4
MC 4  
outputs PG / MC4
MC 4  
Ground base plate
Yes  
Test standards USA
UL 1449 ed.3  
Homologation
VDE, ÖVE und UL  
Test standards Germany
 
Test standards France
UTE C61-740-51  
Test standards Germany
 
Test standards USA
UL 1449 ed.3  
Test standards France
UTE C61-740-51  
   
Article No. E-Number SPD type Operation voltage max. [Uc] Impulse current [Iimp]_(10/350) max. discharge current (Imax) Response time [ta] Voltage protection level [Up] Nominal cross section conductor (min/max) Signaling contact Nominal discharge surge current (8/20) Number of poles comment VPE Quantity
   
Junction box PVGAK+60VG-1000-4ST-2MPP MC4 296.050.250 969 112 314 T1 / T2 ≤1200VDC 12.5 40 ≤25 2.8 6.0 - 35.0 Yes 20 2 a) 1
Junction box PV GAK+50 PVS-1000-4ST-2MPP MC4 296.050.850 969 112 464 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.6 2.5 - 25.0 Yes 15 2 b) 1
Junction box PV GAK+50VG-1000-4ST-2MPP MC4 296.050.450 969 112 364 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.8 2.5 - 25.0 Yes 2 c) 1
Junction box PVGAK+50-1000-4ST-2MPP MC4 296.050.650 969 112 414 T2 ≤1200VDC 5 40 ≤25 2.6 2.5 - 25.0 Yes 15 2 d) 1
Junction box PVGAK+60VG-1000-3ST-1MPP/1ST-1MPP MC4 296.050.272 969 112 324 T1 / T2 ≤1200VDC 12.5 40 ≤25 2.8 6.0 - 35.0 Yes 20 2 e) 1
Junction box PV GAK+50 PVS-1000-3ST-1MPP/1ST-1MPP 296.050.872 969 112 474 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.6 2.5 - 25.0 Yes 15 2 f) 1
Junction box PV GAK+50VG-1000-3ST-1MPP/1ST-1MPP 296.050.472 969 112 374 T1 / T2 ≤1200VDC 6.25 40 ≤25 2.8 2.5 - 25.0 Yes 2 g) 1
Junction box PVGAK+50-1000-3ST-1MPP/1ST-1MPP MC4 296.050.672 969 112 424 T2 ≤1200VDC 5 40 ≤25 2.6 2.5 - 25.0 Yes 15 2 h) 1