Categories
Article No. 296.044.014
E-Number 808 414 020
Technical specification
SPD type T2  
Number of poles 4  
max. discharge current (Imax) 40 kA  
Response time [ta] 0 ns  
Voltage protection level [Up] 1.25 kV  
Nominal cross section conductor (min/max) 0.0 - 42.0 mm²
Nominal discharge surge current (8/20) 20 kA  
Signaling contact Yes  
Nominal frequency [fn] 50.0 - 60.0 Hz
Nominal line voltage Un AC 230 V  
Continuous voltage AC max. 275 V  
Discharge current max. (8/20) µs [Imax] 40 kA  
Protection level max. (at 5kA) 0.9 kV  
Follow current [IF] 0 kA  
follow current extinguishing capability [Ifi] unendlich kA eff  
TOV-voltage L-N [UT] 440 Vac  
Short circuit resistance (Icw) 25 kA  
Fault indication Mechanisch, Rot  
Temperature range -40.0 - 85.0 °C
Degree of protection IP20  
Fuse max. (gG) 125 A  
Mounting on Hutschiene 35 mm  
Material housing  
Signaling on the device Optic  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
System configuration TN-S  
Short-circuit-proof Yes  
Category type 2 Yes  
Mounting method DIN rail (top hat rail) 35 mm  
With remote signalling contact Yes  
20/Pol  
Integrated backup fuse No  
Voltage protection level L-N [Up] 1.25 kV  
Degree of protection (IP) IP20  
Construction size 4 modular spacing  
Standards
Test standards Germany  
Test standards International IEC 61643-11  
Test standards USA UL 1449 ed.3  
Test standards Europe EN 61643-11  
Homologation VDE, ÖVE, UL  
Commercial specification
Customs number 85363000  
country of origin NUL  
Logistic specification
VPE Weight 0.37 kg  
Replacement module

Replacement module 296.044.000

More
Replacement module

Replacement module 296.144.000

More