Categories
Article No. 296.222.102
E-Number 808 486 040
Technical specification
SPD type T1 / T2  
Number of poles 2  
Signaling contact Yes  
Impulse current [Iimp]_(10/350) 5 kA  
max. discharge current (Imax) 40 kA  
Operation voltage max. [Uc] ≤1200VDC  
Response time [ta] 0 ns  
Voltage protection level [Up] 2.8 kV  
Nominal cross section conductor (min/max) 2.5 - 25.0 mm²
Discharge current max. (8/20) µs [Imax] 60 kA  
Operating current [Ic] 0 kA  
Follow current [IF] 0 kA  
follow current extinguishing capability [Ifi] Unendlich kA eff  
Short circuit resistance (Icw) 10 kA  
Fault indication Mechanisch, Rot  
Temperature range -40.0 - 85.0 °C
Material housing  
Signaling on the device Optic  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
Energetically coordinated protective effect to the terminal Yes  
Exhausting No  
Nominal voltage DC 1000 V  
Mounting method DIN rail (top hat rail) 35 mm  
Construction size 3 modular spacing  
System configuration DC Yes  
Integrated backup fuse No  
15/Pol  
Degree of protection (IP) IP20  
Standards
Test standards Germany  
Test standards USA UL 1449 ed.3  
Test standards Europe EN 50539-11  
Test standards France UTE C61-740-51  
Homologation VDE, ÖVE und UL  
Commercial specification
Customs number 85363000  
country of origin RC  
Logistic specification
VPE Weight 0.3 kg  
Kilo / piece 0.3 kg  
Kilo / PU 0.3 kg  
Junction box PV

Junction box PV GAK CiPlug1-XS-AF

More
Junction box PV

Junction box PV GAK CiPlug2-XS-AF

More
Junction box PV

Junction box PV GAK CiPlug3-XS-AF

More
Junction box PV

Junction box PV GAK CiPlug4-XS-AF

More