Article No. 296.480.391
E-Number 808 486 320
Technical specification
SPD type T2  
Signaling contact Yes  
max. discharge current (Imax) 40 kA  
Operation voltage max. [Uc] ≤1200VDC  
Response time [ta] 0 ns  
Voltage protection level [Up] 2.6 kV  
Nominal discharge surge current (8/20) 15 kA  
Number of poles 2  
Short circuit resistance (Icw) 1 kA  
Fault indication mechanisch, Rot  
Temperature range -40.0 - 85.0 °C
Material housing Thermoplastik PEI UL-94-V0  
Signaling on the device Optic  
Connection cross section solid / stranded max. 1.5 mm²  
Switching capacity signaling contact 250 V/0,5 A (AC) / - 30 V / 2 A (DC)  
Energetically coordinated protective effect to the terminal Yes  
Exhausting No  
Nominal voltage DC 1000 V  
Mounting method DIN rail (top hat rail) 35 mm  
Construction size 3 modular spacing  
System configuration DC Yes  
Integrated backup fuse No  
15/Pol  
Total discharge current (8/20) (L N-PE) 60 kA  
Connection cross section (min/max) 2.0 - 25.0 mm²
Degree of protection (IP) IP20  
Follow current [IF] 0 kA  
Standards
Test standards Germany  
Test standards USA UL 1449 ed.3  
Test standards Europe EN 50539-11  
Test standards France UTE C61-740-51  
Commercial specification
Customs number 85363000  
country of origin NUL