Overvoltage protection T1+T2+T3 DS 130 VGS
Characteristics
- surge protector type 1+2+3
- 10 years warranty
- limp = 12.5kA/pole (10/350µs)
- optimized to TOV
- internal disconnection, status indicator
- follow and operating current: none
- remote signaling
SPD type
T1 / T2 / T3
Impulse current [Iimp]_(10/350)
12.5 kA
max. discharge current (Imax)
50 kA
Response time [ta]
≤20 ns
Voltage protection level [Up]
1.25 kV
Nominal cross section conductor (min/max)
2.5 - 25.0 mm²
Signaling contact
Yes
Nominal discharge surge current (8/20)
20 kA
Nominal frequency [fn]
0.0 - 100.0 Hz
Nominal line voltage Un AC
230 V
Continuous voltage AC max.
275 V
Discharge current max. (8/20) µs [Imax]
50 kA
Combined shock [Uoc]
20 kV
Protection level max. (at Imax)
1.25 kV
Operating current [Ic]
0 kA
Follow current [IF]
0 kA
follow current extinguishing capability [Ifi]
Unendlich kA eff
TOV-voltage L-N [UT]
335 V / 5 sec.
TOV-voltage L-PE [UT]
1200 V / 200 ms / 300 A
Short circuit resistance (Icw)
25 kA
Fault indication
Mechanisch, Rot
Temperature range
-40.0 - 85.0 °C
Degree of protection
IP 20
Fuse max. (gG)
160 A
Mounting on
Hutschiene 35 mm
Material housing
Signaling on the device
Optic
Connection cross section solid / stranded max.
1.5 mm²
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)
Energetically coordinated protective effect to the terminal
Yes
Integrated backup fuse
No
Exhausting
No
Mounting method
DIN rail (top hat rail) 35 mm
Yes
Remote signalling
Yes
Total discharge current (8/20) (L N-PE)
50 kA
Degree of protection (IP)
IP20
Test standards Germany
Test standards International
IEC 61643-11
Test standards USA
UL 1449 ed.3
Test standards Europe
EN 61643-11
Homologation
VDE, ÖVE und UL