Categories

Overvoltage protection T1+T2+T3 DS 250 VG

Characteristics
- surge protector type 1+2+3
- 10 years warranty
- limp = 25kA/pole (10/350µs)
- optimized to TOV
- internal disconnection, status indicator
- follow and operating current: none
- remote signaling

SPD type
T1 / T2 / T3  
Impulse current [Iimp]_(10/350)
25 kA  
max. discharge current (Imax)
70 kA  
Response time [ta]
≤20 ns  
Voltage protection level [Up]
1.5 kV  
Nominal discharge surge current (8/20)
30 kA  
Nominal cross section conductor (min/max)
6.0 - 50.0 mm²
Signaling contact
Yes  
Nominal frequency [fn]
0.0 - 100.0 Hz
Nominal line voltage Un AC
230 V  
Continuous voltage AC max.
255 V  
Discharge current max. (8/20) µs [Imax]
70 kA  
Combined shock [Uoc]
20 kV  
Operating current [Ic]
0 kA  
Follow current [IF]
0 kA  
follow current extinguishing capability [Ifi]
Unendlich kA eff  
TOV-voltage L-N [UT]
450 V / 5 sec.  
TOV-voltage N-PE [UT]
1200 V / 200 ms / 300 A  
TOV-voltage L-PE [UT]
1454 V / 200 ms / 300 A  
Short circuit resistance (Icw)
25 kA  
Fault indication
mechanisch, Rot  
Temperature range
-40.0 - 85.0 °C
Degree of protection
IP20  
Fuse max. (gG)
315 A  
Mounting on
Hutschiene 35 mm  
Material housing
 
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Switching capacity signaling contact
250 V/0,5 A (AC) / 125 V/0,25 A (DC)  
Energetically coordinated protective effect to the terminal
Yes  
Exhausting
No  
Yes  
Voltage protection level L-N [Up]
1.5 kV  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
Protection level max. (at 5kA)
0.65 kV  
Protection level max. (at 12.5kA)
0.8 kV  
Protection level max. (at Imax)
1.5 kV  
Test standards Germany
 
Test standards International
IEC 61643-11  
Test standards USA
UL 1449 d.3  
Test standards Europe
EN 61643-11  
Homologation
UL  
   
Article No. E-Number SPD type Number of poles Impulse current [Iimp]_(10/350) max. discharge current (Imax) Response time [ta] Voltage protection level [Up] Nominal discharge surge current (8/20) Nominal cross section conductor (min/max) Signaling contact Nominal frequency [fn] VPE Quantity
   
Surge Protector 296.901.374 808 451 020 T1 / T2 / T3 1 25 70 ≤20 1.5 30 6.0 - 50.0 Yes 0.0 - 100.0 1
Surge Protector 296.902.374 808 453 010 T1 / T2 / T3 3 25 70 ≤20 1.5 30 6.0 - 50.0 Yes 0.0 - 100.0 1
Surge Protector 296.900.374 808 454 010 T1 / T2 / T3 4 25 70 ≤20 1.5 30 6.0 - 50.0 Yes 0.0 - 100.0 1