Overvoltage protection T3 DS 415 S/G
Characteristics
- surge protector type 3
- In = 5kA; Imax = 15kA
- internal disconnection, status indicator
- pluggable module
- remote signaling
SPD type
T3
Number of poles
4
Signaling contact
Yes
max. discharge current (Imax)
15 kA
Response time [ta]
0 ns
Voltage protection level [Up]
0.9 kV
Nominal cross section conductor (min/max)
1.5 - 10.0 mm²
Nominal discharge surge current (8/20)
5 kA
Nominal frequency [fn]
50.0 - 60.0 Hz
Nominal line voltage Un AC
230 V
Continuous voltage AC max.
275 V
Discharge current max. (8/20) µs [Imax]
15 kA
Combined shock [Uoc]
10 kV
Operating current [Ic]
0 kA
Follow current [IF]
0 kA
follow current extinguishing capability [Ifi]
Unendlich kA eff
TOV-voltage L-N [UT]
335 V / 5 sec.
TOV-voltage N-PE [UT]
1200 V / 300 A / 200ms fest
Short circuit resistance (Icw)
10 kA
Fault indication
Mechanisch, rot
Temperature range
-40.0 - 85.0 °C
Degree of protection
IP20
Fuse max. (gG)
40 A
Mounting on
Hutschiene 35 mm
Material housing
Signaling on the device
Optic
Connection cross section solid / stranded max.
1.5 mm²
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)
System configuration
With interference suppressor filter
No
Nominal discharge surge current (8/20) (L-N)
20 kA
Total discharge current (8/20) (L N-PE)
60 kA
With remote signalling contact
Yes
Mounting method
DIN rail (top hat rail) 35 mm
5/Pol
Category type 3
Yes
Voltage protection level L-N [Up]
0.9 kV
Degree of protection (IP)
IP20
Construction size
2 modular spacing
Test standards Germany
Test standards International
IEC 61643-11
Test standards USA
UL 1449 ed.3
Test standards Europe
EN 61643-11
Homologation
VDE, ÖVE und UL