Overvoltage protection T2+T3 DS 40 VGS
Characteristics
- surge protector type 2+3
- 10 years warranty
- In = 20kA; Imax = 40kA
- optimized to TOV
- internal disconnection, status indicator
- pluggable module
- follow and operating current: none
- remote signaling
SPD type
T2 / T3
max. discharge current (Imax)
40 kA
Response time [ta]
≤20 ns
Voltage protection level [Up]
1.1 kV
Nominal cross section conductor (min/max)
2.5 - 25.0 mm²
Nominal frequency [fn]
0.0 - 100.0 Hz
Nominal discharge surge current (8/20)
20 kA
Signaling contact
Yes
Nominal line voltage Un AC
230 V
Continuous voltage AC max.
275 V
Combined shock [Uoc]
10 kV
Protection level max. (at 5kA)
0.8 kV
Protection level max. (at 12.5kA)
0.95 kV
Protection level max. (at Imax)
1.5 kV
Operating current [Ic]
0 kA
Follow current [IF]
0 kA
follow current extinguishing capability [Ifi]
Unendlich kA eff
TOV-voltage L-N [UT]
450 V / 5 sec.
Short circuit resistance (Icw)
25 kA
Fault indication
Mechanisch, Rot
Temperature range
-40.0 - 85.0 °C
Degree of protection
IP20
Fuse max. (gG)
125 A
Mounting on
Hutschiene 35 mm
Signaling on the device
Optic
Connection cross section solid / stranded max.
1.5 mm²
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)
Category type 2
Yes
Voltage protection level L-N [Up]
1.1 kV
20/Pol
Short-circuit-proof
Yes
Integrated backup fuse
No
With remote signalling contact
Yes
Mounting method
DIN rail (top hat rail) 35 mm
Degree of protection (IP)
IP20
Material housing
Test standards Germany
Test standards International
IEC 61643-11
Test standards USA
UL 1449 ed.3
Test standards Europe
EN 61643-11
Homologation
VDE, ÖVE und UL