Categories

Overvoltage protection T2+T3 DS 40 VGS

Characteristics
- surge protector type 2+3
- 10 years warranty
- In = 20kA; Imax = 40kA
- optimized to TOV
- internal disconnection, status indicator
- pluggable module
- follow and operating current: none
- remote signaling

Nominal line voltage Un AC
230 V  
Continuous voltage AC max.
275 V  
Combined shock [Uoc]
10 kV  
Protection level max. (at 5kA)
0.8 kV  
Protection level max. (at 12.5kA)
0.95 kV  
Protection level max. (at Imax)
1.5 kV  
Operating current [Ic]
0 kA  
Follow current [IF]
0 kA  
follow current extinguishing capability [Ifi]
Unendlich  
TOV-voltage L-N [UT]
450 V / 5 sec.  
Short circuit resistance (Icw)
25 kA  
Fault indication
Mechanisch, Rot  
Degree of protection
IP20  
Fuse max. (gG)
125 A  
Mounting on
Hutschiene 35 mm  
Material housing
Thermoplast PEI UL-94-5VA  
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
Category type 2
Yes  
Voltage protection level L-N [Up]
1.1 kV  
Short-circuit-proof
Yes  
Integrated backup fuse
No  
With remote signalling contact
Yes  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
Homologation
VDE, ÖVE und UL  
Test standards International
IEC 61643-11  
Test standards USA
UL 1449 ed.3  
Test standards Europe
EN 61643-11  
   
Article No. E-Number SPD type Number of poles max. discharge current (Imax) Response time [ta] Voltage protection level [Up] Nominal cross section conductor Nominal frequency [fn] Nominal discharge surge current (8/20) Signaling contact VPE Quantity
   
Surge Protector 296.044.051 808 471 000 T2 / T3 1 40 ≤20 1.1 2.5 - 25 0 - 100 20 Yes 1
Surge Protector 296.044.052 808 476 000 T2 / T3 2 40 ≤20 1.1 2.5 - 25 0 - 100 20 Yes 1
Surge Protector 296.044.053 808 477 000 T2 / T3 3 40 ≤20 1.1 2.5 - 25 0 - 100 20 Yes 1
Surge Protector 296.044.054 808 478 000 T2 / T3 4 40 ≤20 1.1 2.5 - 25 0 - 100 20 Yes 1