Categories

Overvoltage protection T1+T2+T3 DS 250 VG

Characteristics
- surge protector type 1+2+3
- 10 years warranty
- limp = 25kA/pole (10/350µs)
- optimized to TOV
- internal disconnection, status indicator
- follow and operating current: none
- remote signaling

Nominal line voltage Un AC
230 V  
Continuous voltage AC max.
255 V  
Discharge current max. (8/20) µs [Imax]
70 kA  
Combined shock [Uoc]
20 kV  
Protection level max. (at 5kA)
0.65 kV  
Protection level max. (at 12.5kA)
0.8 kV  
Protection level max. (at Imax)
1.5 kV  
Operating current [Ic]
0 kA  
Follow current [IF]
0 kA  
follow current extinguishing capability [Ifi]
Unendlich  
TOV-voltage L-N [UT]
450 V / 5 sec.  
TOV-voltage N-PE [UT]
1200 V / 200 ms / 300 A  
TOV-voltage L-PE [UT]
1454 V / 200 ms / 300 A  
Short circuit resistance (Icw)
25 kA  
Fault indication
mechanisch, Rot  
Degree of protection
IP20  
Fuse max. (gG)
315 A  
Mounting on
Hutschiene 35 mm  
Material housing
Thermoplast PEI UL-94-5VA  
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Switching capacity signaling contact
250 V/0,5 A (AC) / 125 V/0,25 A (DC)  
Energetically coordinated protective effect to the terminal
Yes  
Exhausting
No  
Network configuration
Yes  
Voltage protection level L-N [Up]
1.5 kV  
Mounting method
DIN rail (top hat rail) 35 mm  
Degree of protection (IP)
IP20  
Homologation
UL  
Test standards Europe
EN 61643-11  
Test standards International
IEC 61643-11  
Test standards USA
UL 1449 d.3  
   
Article No. E-Number SPD type Number of poles Impulse current [Iimp]_(10/350) max. discharge current (Imax) Response time [ta] Voltage protection level [Up] Nominal discharge surge current (8/20) Nominal cross section conductor Signaling contact VPE Quantity
   
Surge Protector 296.901.374 808 451 020 T1 / T2 / T3 1 25 70 ≤20 1.5 30 6 - 50 Yes 1
Surge Protector 296.902.374 808 453 010 T1 / T2 / T3 3 25 70 ≤20 1.5 30 6 - 50 Yes 1
Surge Protector 296.900.374 808 454 010 T1 / T2 / T3 4 25 70 ≤20 1.5 30 6 - 50 Yes 1