Categories

Overvoltage protection T3 DS 215

Characteristics
- surge protector type 3
- In = 5kA; Imax = 15kA
- internal disconnection, status indicator
- pluggable module
- remote signaling

Nominal line voltage Un AC
230 V  
Continuous voltage AC max.
250 V  
Discharge current max. (8/20) µs [Imax]
15 kA  
Combined shock [Uoc]
10 kV  
Operating current [Ic]
0 kA  
Follow current [IF]
0 kA  
follow current extinguishing capability [Ifi]
unendlich  
TOV-voltage L-N [UT]
250 V / 5 sec.  
TOV-voltage N-PE [UT]
1200 V / 300 A / 200ms fest  
Short circuit resistance (Icw)
10 kA  
Fault indication
Mechanisch, Rot  
Degree of protection
IP20  
Fuse max. (gG)
40 A  
Mounting on
Hutschiene 35 mm  
Signaling on the device
Optic  
Connection cross section solid / stranded max.
1.5 mm²  
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)  
Nominal discharge surge current (8/20) (L-N)
5 kA  
With interference suppressor filter
No  
Total discharge current (8/20) (L N-PE)
15 kA  
Mounting method
DIN rail (top hat rail) 35 mm  
Category type 3
Yes  
With remote signalling contact
Yes  
Voltage protection level L-N [Up]
1.5 kV  
Degree of protection (IP)
IP20  
Construction size
1 modular spacing  
Homologation
VDE, ÖVE, UL  
Test standards International
IEC 61643-11  
Test standards USA
UL 1449 ed.3  
Test standards Europe
EN 61643-11  
   
Article No. E-Number SPD type Number of poles Signaling contact max. discharge current (Imax) Response time [ta] Voltage protection level [Up] Nominal cross section conductor Nominal discharge surge current (8/20) VPE Quantity
   
Surge Protector 296.045.714 808 406 800 T3 2 Yes 15 ≤20 0.9 1.5 - 10 5 1