Overvoltage protection T1+T2 DS 130 RS
Characteristics
- surge protector type 1+2
- limp = 12.5kA/pole (10/350µs
- optimized to TOV
- pluggable module
- remote signaling
Nominal line voltage Un AC
230 V
Discharge current max. (8/20) µs [Imax]
50 kA
Follow current [IF]
0 kA
follow current extinguishing capability [Ifi]
unendlich
TOV-voltage L-N [UT]
440 Vac
Short circuit resistance (Icw)
25 kA
Fault indication
Mechanisch, Rot
Degree of protection
IP 20
Fuse max. (gG)
160 A
Mounting on
Hutschiene 35 mm
Signaling on the device
Optic
Connection cross section solid / stranded max.
1.5 mm²
Switching capacity signaling contact
250 V / 0,5 A (AC) - 30 V / 2 A (DC)
Material housing
Thermoplastik UL-94-V0
Remote signalling
Yes
Voltage protection level L-N [Up]
1.3 kV
Total discharge current (8/20) (L N-PE)
50 kA
Homologation
VDE, ÖVE und UL
Test standards International
IEC 61643-11
Test standards USA
UL 1449 ed.3
Test standards Europe
EN 61643-11